Daikin Altherma fault E8-00

Outdoor unit: power input overvoltage

Heat pump

What it means

Compressor running current exceeds standard value for 2.5 seconds, indicating an overvoltage/overcurrent condition on the power input.

Likely causes

  1. Outdoor temperature is out of operation range
  2. Faulty compressor or miswiring of the compressor power supply cable
  3. Faulty inverter PCB
  4. Faulty or disturbance of the power supply (power supply MUST be within range of nominal operating voltage ±4%)
  5. Power drop
  6. Short circuit
  7. Faulty refrigerant pressure sensor
  8. Poor water flow through high pressure side plate heat exchanger
  9. Incorrect refrigerant charge
  10. Compressor guard timer active
  11. Special software control activated - water loop temperature is too low causing ONLY the backup heater to operate
  12. Faulty compressor winding
  13. Faulty expansion valve
  14. Faulty suction thermistor
  15. Blockages in refrigerant circuit
  16. Faulty discharge pipe thermistor
  17. Worn or damaged compressor dampers causing vibration/noise
  18. Normal inverter control behavior when target temperature achieved
  19. Flammable refrigerant remaining dissolved in compressor lubricant
  20. Wrong assembly during repair
  21. Excessive heat applied during brazing near compressor pipes

Where to start

  1. Check the outdoor temperature
  2. Perform a check of the compressor
  3. Perform a check of the inverter PCB

The full answer, free

  • 19 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 40), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.

Other Daikin Altherma fault codes