Joule Victorum fault 80

No temp diff across condensor

Heat pump

What it means

No temperature differential detected across the condenser. This is a temporary blocking fault - the Heat Pump automatically restarts after 1 hour.

Likely causes

  1. Circulating pump not operating correctly
  2. Air in the system
  3. By-pass valve incorrectly set
  4. Zone valve not fully open causing dead heading
  5. Long pipe runs to draw-off points on larger installations

Where to start

  1. Check circulating pump operation
  2. Check for possible air in the system
  3. Ensure system is operating in heating mode with corresponding zone valve fully open

The full answer, free

  • 15 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 96), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.