Samsung Heat pump fault E912
Flow switch close error
Heat pumpWhat it means
Water flow switch is stuck in closed position or continuously detecting flow when it should not
Likely causes
- Flow switch malfunction or stuck
- Flow switch connector short circuit
- Debris in flow switch
- Flow switch wiring shorted
Where to start
- Check flow switch for debris or blockage
- Inspect flow switch connector for shorts
- Measure flow switch resistance
The full answer, free
- 1 more check in order
- How to put it right, step by step
- The manual page for this fault (page 85), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Samsung manual for the Heat pump. Check the model on the data plate before you order parts.
Other Samsung Heat pump fault codes
- E108Setting address duplicate error
- E201CONTROL KIT / outdoor UNIT communication error (matching error)
- E202CONTROL KIT / outdoor UNIT communication error
- E203Communication error between INVERTER and MAIN MICOM (6 min)
- E205Communication error between outdoor unit inv micom - fan motor micom
- E443No startup due to low pressure
- E458Outdoor unit fan error
- E507Comp down due to high pressure or high pressure switch open
- E563INDOOR UNIT mixed install error
- E904Water tank sensor short/open
- E906Outdoor EVA in sensor error
- E907Pipe rupture protection error
- E910Water temperature sensor detached
- E911Minimum water flow rate not met
- E913Flow switch error detected six times (re-operation impossible)
- E914Incorrect thermostat connection
- E915DC fan non-operating
- E916Mixing sensor short/open