Trianco High Temperature Air Source Heat Pump R290 fault F05
DC bus over voltage
Heat pumpWhat it means
DC bus over voltage protection.
Likely causes
- Fan Blade or motor issue
- EEV step is not suitable
- Refrigerant amount incorrect
- Parameter Issue
- Compressor Issue
- Fan not running or speed is too low
- Refrigerant leak
- Loose screws
- Touching components
Where to start
- Check the voltage between DCP-IN and DCN-IN if lower than 300V, the unit will get this protection
- Check the input voltage of R/S/T on compressor driver board if lower than 210V, the unit will get this protection
- If they are OK, please replace a new compressor driver board
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 35), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Trianco manual for the High Temperature Air Source Heat Pump R290. Check the model on the data plate before you order parts.
Other Trianco High Temperature Air Source Heat Pump R290 fault codes
- E03Water flow switch protection
- E08Communication fault
- E103Fan motor overload protection
- F03PFC fault
- F06DC bus under voltage
- F07AC input under voltage
- F09Input voltage sampling fault
- F26IGBT power device overheat fault
- P01Water inlet temp. sensor fault
- P02Water outlet temp. sensor fault
- P032Hot water tank temp. sensor fault
- P04Ambient temp. sensor fault
- P101EVI inlet temp. sensor fault
- P102EVI outlet temp. sensor fault
- P153Coil temp. sensor fault
- P17Water outlet temp. sensor fault
- P181Exhaust temp. sensor fault
- P182Exhaust over temp
- P191Antifreeze temp. sensor fault
- P42Room temp. sensor fault