Midea R32 M thermal Arctic Mono fault L4

MCE error

Heat pump

What it means

MCE error detected by refrigerant system main PCB. Displayed as P6/H4 on user interface.

Likely causes

  1. Compressor is over-current
  2. Inverter PCB has malfunctioned
  3. Inverter module damaged
  4. DC bus low voltage protection
  5. DC bus high voltage protection
  6. Software over current protection
  7. Inverter PCB failure (if appears immediately on power-on)
  8. Compressor over-current (if appears during running at speed over 60rps)
  9. Inverter PCB failure (if compressor current is normal during running condition)
  10. Inverter module has overheated
  11. Inverter module is over-current (compressor failure)
  12. Inverter module failed
  13. Motor control error
  14. Discharge temperature exceeding 105°C indicating high compressor load or high ambient/system conditions
  15. Compressor current exceeding Currentmax threshold

Where to start

  1. Restart unit
  2. Use clip-on ammeter to measure compressor current
  3. Check: Is the inverter module damaged? Measure the resistance between each of U, V and W and each of P and N on the inverter module.

The full answer, free

  • 29 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 67), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.