Grant Aerona R290 fault 6

Pump block protection

Heat pump

What it means

Pump block protection has activated; pump will automatically re-start after 5 seconds.

Likely causes

  1. Pump rotor blocked or stuck
  2. Impurities in pump
  3. Poor pump performance
  4. Fuse is burnt out
  5. Connection to PCB is loose or disconnects
  6. Pump failure
  7. Too low voltage
  8. Pump rotors are stuck
  9. Gas in the pump
  10. Inlet pressure too low
  11. Flow regulators or restrictors fitted in circuit
  12. Valves not fully open causing flow restriction
  13. Outside air temperature at or below 6°C
  14. System water temperature at or below 6°C
  15. External electrical isolator switched to OFF position
  16. Heat pump switched OFF at the controller
  17. No demand from heating system controls
  18. Outdoor temperature too high to call heat pump on (weather regulated zones)
  19. Active error code present on controller
  20. Outdoor temperature too high for weather compensated zones to call heat pump
  21. Active error code on controller display
  22. Insufficient flow rate through primary circuit
  23. PWM circulating pump not modulating correctly
  24. Blockage or air in primary circuit
  25. Pump fault or blockage causing low flow
  26. External electrical isolator switched OFF for extended period during cold weather

Where to start

  1. Check pump rotor for free movement
  2. Inspect for impurities/debris in pump
  3. Check inlet water pressure

The full answer, free

  • 40 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 85), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Grant manual for the Aerona R290. Check the model on the data plate before you order parts.