Midea M-Thermal Arctic HT R290 Mono fault E6
T4 ambient temperature sensor error
Heat pumpWhat it means
Fault relating to the T4 ambient temperature sensor.
Likely causes
- Loose, misconnected, broken or moisturized sensor connection
- Sensor short-circuit (resistance < 0.5 kΩ)
- Sensor failure (resistance > 380 kΩ)
- Resistance inconsistent with resistance characteristics table
- Sensor probe dislodged from installation position
- Main Control PCB failure
- Sensor fault or wiring fault at CN45 port
- Water temperature sensor resistance does not match expected characteristics table value
- Set temperature reached
Where to start
- Step 1: Check if temperature sensor connection on Main Control PCB is loose, misconnected, broken or moisturized. If yes, reconnect the temperature sensor correctly and keep it dry.
- Step 2: If connection is fine, pull out the temperature sensor and measure sensor resistance. If resistance is too low (<0.5 kΩ), sensor has short-circuited. If resistance is too high (>380 kΩ), sensor has failed. Compare to the resistance characteristics table in Part 4 Appendix; if inconsistent, sensor has failed. Replace the sensor if so.
- Step 3: If resistance test is normal, check fixed position of sensor and whether sensor probe has fallen off. If yes, re-fix the sensor firmly to the installation position.
The full answer, free
- 15 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 108), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection