Midea M-Thermal Arctic HT R290 Mono fault FC1
TL outdoor unit heat exchanger outlet temperature sensor error
Heat pumpWhat it means
Fault relating to the TL outdoor unit heat exchanger outlet temperature sensor.
Likely causes
- Loose, misconnected, broken or moisturized sensor connection
- Sensor short-circuit (resistance < 0.5 kΩ)
- Sensor failure (resistance > 380 kΩ)
- Resistance inconsistent with resistance characteristics table
- Sensor probe dislodged from installation position
- Main Control PCB failure
- Sensor fault or wiring fault at CN7 port
- Water temperature sensor resistance does not match expected characteristics table value
- Set temperature reached
Where to start
- Step 1: Check if temperature sensor connection on Main Control PCB is loose, misconnected, broken or moisturized. If yes, reconnect the temperature sensor correctly and keep it dry.
- Step 2: If connection is fine, pull out the temperature sensor and measure sensor resistance. If resistance is too low (<0.5 kΩ), sensor has short-circuited. If resistance is too high (>380 kΩ), sensor has failed. Compare to the resistance characteristics table in Part 4 Appendix; if inconsistent, sensor has failed. Replace the sensor if so.
- Step 3: If resistance test is normal, check fixed position of sensor and whether sensor probe has fallen off. If yes, re-fix the sensor firmly to the installation position.
The full answer, free
- 15 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 108), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection