Midea M-Thermal Arctic HT R290 Mono fault H1
Communication error between main control PCB and inverter PCB
Heat pumpWhat it means
Communication failure occurs between the Main Control PCB and the Inverter PCB, triggered after powering on the unit for 2 minutes.
Likely causes
- Abnormal power supply to ODU (outside 190-264V range)
- Inverter PCB LED2 off indicating inverter fault
- Faulty or disconnected communication cable from CN43
- Faulty Main Control PCB
- Inverter PCB fault (LED2 off or abnormal BUS voltage)
- Faulty communication cable between Main Control PCB and Inverter PCB (CN43)
Where to start
- Check whether power supply for ODU is abnormal (normal range is 190-264V); if abnormal, adjust power supply
- If power supply normal, check whether the LED2 on inverter PCB is off, or the bus voltage between P,N is greater than 280VDC
- If LED2 off or bus voltage >280VDC, measure the voltage of the fifth and sixth pin of CN43 on Main Control PCB; if not around 12VDC, replace the Main Control PCB; if it is around 12VDC, replace the inverter control box
The full answer, free
- 18 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 105), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection