Midea M-Thermal Arctic HT R290 Mono fault EA
Low discharge temperature protection
Heat pumpWhat it means
Protects the compressor when discharge temperature (Tp) is below suction temperature (Th) for more than 12 minutes after compressor operates. Also triggered by running time ≥12 mins with Tp<-20°C or Tp<Th lasting 30s.
Likely causes
- Discharge temperature abnormally low relative to suction temperature Expansion valve stuck open, refrigerant overcharge, compressor valve leakage, low load condition
- Loose, misconnected, broken or moisturized sensor connection
- Sensor short-circuit (resistance < 0.5 kΩ)
- Sensor failure (resistance > 380 kΩ)
- Resistance inconsistent with resistance characteristics table
- Sensor probe dislodged from installation position
- Main Control PCB failure
- Discharge temperature below suction temperature for extended period
- Low refrigerant charge or flow issue causing insufficient discharge superheat
- Tp<-20°C condition or Tp<Th lasting 30s during compressor run
- Flow switch leak due to faulty sealing ring
- Pump idling due to insufficient water/air in circuit
- Feedback signal cable CN17 not connected properly
- Water temperature sensor resistance does not match expected characteristics table value
- Unit capacity not matched to the system (oversized or undersized)
- Heat exchanger coil in DHW tank too small (insufficient heat exchange area)
- Insufficient water volume in system / high water side resistance due to lack of buffer tank
- Water pump leak due to faulty sealing ring
- Flow switch FS plug (CN8) is not connected properly
- The water flow in the pipe is not consistent with arrow on the flow switch
- Water flow switch mechanically damaged (rake does not trigger contact closure)
- Abnormal state detected requiring compressor protection
- Set temperature reached (normal stop)
- Abnormal system state detected
Where to start
- Monitor discharge temperature (Tp) and suction temperature (Th) during compressor operation
- Track compressor running time against 12 minute threshold for EA logic
- Monitor discharge and suction temperatures, check expansion valve operation, verify system load Monitor discharge and suction temperature differential for duration exceeding 5 minutes Monitor discharge temperature versus suction temperature for duration exceeding 5 minutes Monitor discharge temperature versus suction temperature for duration exceeding 5 minutes Monitor discharge and suction temperatures, check expansion valve operation, verify system load
The full answer, free
- 32 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 28), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection