Midea M-Thermal Arctic HT R290 Mono fault HH
Repeated DC fan motor protection lockout
Heat pumpWhat it means
Escalation fault displayed when H6 (DC fan motor protection) occurs 10 times within 120 minutes, requiring manual intervention.
Likely causes
- Persistent fan motor failure, chronic power supply issue, repeated fan obstruction
- Repeated fan connection cable faults
- Repeated fan motor failure
- Repeated inverter PCB failure
- Repeated H6 fan motor protection events (10 times within 120 minutes)
- Persistent fan motor or power supply fault causing repeated low-speed trips
Where to start
- Investigate root cause of repeated H6 protection events, repair or replace fan motor
- Power off the unit and check if the fan connection cables are disconnected or misconnected; if yes, reconnect the cables correctly
- Use a digital multimeter to measure the resistance between each two of fan terminals; if the resistance is <10 Ohm, fan motor failed - replace the fan
The full answer, free
- 5 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 28), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error