Midea M-Thermal Arctic HT R290 Mono fault P1
High pressure protection
Heat pumpWhat it means
The system protects the refrigerant circuit from abnormally high discharge pressure and protects the compressor from transient pressure spikes. When discharge pressure (Pc) rises above 3.5MPa, the unit stops running and displays P1.
Likely causes
- High-pressure switch plug from the inverter control box is loose or misconnected
- Faulty high-pressure switch
- Fan not running normally (fan motor or inverter PCB failure)
- Refrigerant overcharge
- Refrigerant charge issue
- Refrigerant system fault causing pressure spike
- Refrigerant leak from container or system
Where to start
- Check if the high-pressure switch plug from the inverter control box is loose or misconnected. If yes, reconnect high-pressure switch securely.
- Power off and power on again. If P1 error still occurs, use a digital multimeter to measure high-pressure switch with buzzer. If buzzer doesn't sound, replace high-pressure switch. If buzzer sounds, replace inverter control box.
- Reboot the unit and check 'Unit Status-Operation parameter-P1 comp. pressure' on the User Interface. Confirm P1 comp. pressure >3.5MPa when the P1 error occurred. If yes, replace the high-pressure switch.
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 27), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error