Midea M-Thermal Arctic HT R290 Mono fault P4
High discharge temperature protection
Heat pumpWhat it means
Protects the compressor from abnormally high discharge temperatures and transient spikes. Triggered when discharge temperature rises above 115°C.
Likely causes
- Faulty Tp discharge temperature sensor
- Tw_in/Tw_out sensor dislodged from installation port
- Faulty Tw_in or Tw_out temperature sensor
- Refrigerant leakage
- Abnormally high discharge temperature
- Transient temperature spikes in the compressor discharge line
- Abnormal state detected requiring compressor protection
- Set temperature reached (normal stop)
- Abnormal system state detected
Where to start
- Monitor discharge temperature (Tp) and suction temperature (Th) during compressor operation
- Track compressor running time against 12 minute threshold for EA logic
- If sensors are correctly installed, pull out Tw_out/Tw_in sensor from plate heat exchanger, leave it in the air for 10 mins; if the temperature difference between sensor and air is greater than 5°C, the sensor failed. Alternatively measure resistance and compare with sensor's resistance characteristics table (Appendix 4); if not consistent, the sensor has failed.
The full answer, free
- 12 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 28), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- EBTsolar solar panel temperature sensor error
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error